The rule
Recycled water systems feeding water closets, urinals, and trap primers have to deliver at least 15 psi of residual pressure at the highest and most remote outlet they serve. If the pressure in the recycled water system inside the building is over 80 psi, a pressure-reducing valve has to bring it down to 80 psi or less at the outlets.
The same text carries the next few rules too (listed in the code as 1505.6 through 1505.8). Before the building is occupied or the system is activated, the installer runs an initial cross-connection test in front of the Authority Having Jurisdiction, and it has to be ruled successful before final approval. Recycled water supply and distribution materials follow the same requirements as potable water piping unless the section says otherwise.
Color and marking: control valves and other mechanical equipment on the recycled system are painted purple or made of purple material matching Pantone 512 or 522C. The piping is permanently marked in clearly visible black uppercase letters on a purple background. You can do that with purple adhesive Mylar PVC tape (Pantone 512) along the entire length of the pipe, or with pipe made with purple integral to the material. The wording is CAUTION: NONPOTABLE RECYCLED WATER, DO NOT DRINK, and it has to be installed so the words are clearly visible.
On the job
- Check pressure at the farthest toilet or urinal, not at the meter. The 15 psi requirement is residual pressure at the highest and most remote outlet.
- If you're taping existing pipe, put the tape on the entire length and turn it so the wording faces out where people can read it.
- Make sure valves and equipment get painted or are purple from the factory. A purple pipe with a gray valve is a correction.
The inspector and your city's adopted edition have the final word.