The rule
The starting point is that building or changing a rainwater catchment system in a building or on a premises needs a permit from the Authority Having Jurisdiction. That's true even when you're a homeowner with a barrel and a pump.
Exception one covers exterior systems used for outdoor non-spray irrigation with a maximum storage capacity of 5000 gallons. All of these have to be true: the tank is supported directly on grade, its height-to-diameter or width ratio doesn't exceed 2 to 1, and the system doesn't need electrical power or a makeup water supply connection.
Exception two, tagged as a housing (HCD) adoption, is for exterior systems used for spray irrigation with a maximum storage capacity of 360 gallons.
If a system doesn't fit an exception, you're in permit territory, with plans (1602.2), listed components, and design requirements in 1601.2. Even where no permit is needed, the system still can't be connected to potable water directly (1602.4).
On the job
- Check all four conditions for the 5000 gallon exception: exterior, non-spray irrigation, tank on grade at 2 to 1 or squatter, no pump or makeup line. One no and it's a permit job.
- A pump, a float-switch makeup line, or an indoor tie-in puts the system in permit territory.
- Tell the customer that no permit doesn't mean no rules. The other code rules still apply, and the city has the final word.
The inspector and your city's adopted edition have the final word.