CPC 1601.3 · Gray water, recycled water and rainwater

Rainwater catchment permits and the no-permit exceptions

A nonpotable rainwater catchment system needs a permit. California exempts outdoor non-spray irrigation tanks up to 5000 gallons if the tank sits on grade, is no taller than 2 to 1 height to diameter or width, and has no power or makeup water connection. Spray irrigation up to 360 gallons is exempt under the housing adoption.

2025 California Plumbing Code, Chapter 16 (Nonpotable Rainwater Catchment Systems) · Applies to: Homes and commercial buildings

A rain tank on grade with a height no more than 2 times its diameter, outdoor non-spray irrigation, 5000 gallon limit, and no pump or makeup water line, next to the spray irrigation 360 gallon exception.
No permit for outdoor non-spray irrigation up to 5000 gal when the tank is on grade, no taller than 2 to 1, with no power and no makeup water. Spray irrigation: 360 gal. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

The starting point is that building or changing a rainwater catchment system in a building or on a premises needs a permit from the Authority Having Jurisdiction. That's true even when you're a homeowner with a barrel and a pump.

Exception one covers exterior systems used for outdoor non-spray irrigation with a maximum storage capacity of 5000 gallons. All of these have to be true: the tank is supported directly on grade, its height-to-diameter or width ratio doesn't exceed 2 to 1, and the system doesn't need electrical power or a makeup water supply connection.

Exception two, tagged as a housing (HCD) adoption, is for exterior systems used for spray irrigation with a maximum storage capacity of 360 gallons.

If a system doesn't fit an exception, you're in permit territory, with plans (1602.2), listed components, and design requirements in 1601.2. Even where no permit is needed, the system still can't be connected to potable water directly (1602.4).

On the job

  • Check all four conditions for the 5000 gallon exception: exterior, non-spray irrigation, tank on grade at 2 to 1 or squatter, no pump or makeup line. One no and it's a permit job.
  • A pump, a float-switch makeup line, or an indoor tie-in puts the system in permit territory.
  • Tell the customer that no permit doesn't mean no rules. The other code rules still apply, and the city has the final word.

The inspector and your city's adopted edition have the final word.