Home › Code Library › CPC 1014.2

CPC 1014.2 · Traps and interceptors

Hydromechanical grease interceptors: flow control, vent, and capacity

Fixtures on a hydromechanical grease interceptor discharge through an approved vented flow control in a visible, accessible spot, and the connected fixtures' total capacity can't exceed two and one-half times the interceptor's certified gpm rating. A vent goes downstream of the interceptor.

2025 California Plumbing Code, Chapter 10 (Traps and Interceptors) · Applies to: Commercial buildings

A sink draining through a vented flow control into a hydromechanical grease interceptor, with a vent downstream, plus the capacity rule of two and one-half times the certified gpm.
Vented flow control upstream, a vent downstream, and fixture capacity no more than 2-1/2 times the gpm rating. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

A hydromechanical interceptor (the small under-counter or floor unit) has a certified flow rate in gpm. The fixtures that feed it have to discharge through an approved vented flow control, installed where people can see and reach it. The flow control can't have adjustable or removable parts, and the flow through it can never exceed the interceptor's rated flow.

The flow control's vent or air inlet ties into the sanitary drainage vent system or goes through the roof. It doesn't terminate to the free air inside the building, and no system vent sits between the flow control and the interceptor inlet. A listed interceptor with an integral flow control is the exception, and it follows the manufacturer's instructions.

For capacity, total the gallons of the fixtures that discharge into the unit (the fixtures, appliances, and equipment that connect to it). That total can't exceed two and one-half times the certified gpm of the interceptor. The code's example works out a compartment sink as length times width times depth, divided by 231, times a 0.75 fill factor, over a drain period of 1 or 2 minutes.

A vent has to be installed downstream of a hydromechanical interceptor.

On the job

  • Use the manufacturer's certified gpm, not the nominal size. A 20 gpm unit can take fixtures totaling up to 50 gallons.
  • A flow control that's hidden behind a panel or can be adjusted by a cook is a rejection. Put it in plain sight and don't use an adjustable type.
  • Count every fixture that drains to the unit when you total it. Add a floor sink or a pre-rinse and the number moves.

The inspector and your city's adopted edition have the final word.

Give us a call

Call (760) 912-9831