The rule
Take the horizontal projected roof area the leader serves and the design rainfall rate, then read the leader size from Table 1103.1. The table gives the maximum roof area for each size at rainfall rates from 1 to 12 inches per hour.
The design storm is a 60 minute, 100 year storm unless the authority having jurisdiction requires something else. Section 1101.12.1 refers you to Table D 101.1 in Appendix D for those rates by location.
For a rainfall rate that isn't in the table, divide the area in the 1 inch per hour column by your rate. A 3 inch leader at 5 inches per hour, for example, serves 8,800 divided by 5, which is 1,760 square feet.
Vertical piping can be round, square, or rectangular. Square pipe has to enclose its equivalent round pipe. Rectangular pipe needs at least the same cross-sectional area, and its sides can't be more than 3 to 1.
On the job
- Projected area is the flat area the rain lands on, not the sloped roof surface.
- Don't pick a rate from memory. Confirm the design rainfall with the plan reviewer or the engineer of record.
- Walls that drain onto a roof add to the area under Section 1103.4. Count them before you size.
The inspector and your city's adopted edition have the final word.