CPC 408.6 · Fixtures

Shower curb, flange and floor slope

A shower curb has to sit at least 1 inch lower than the sides and back, and be between 2 and 9 inches high measured from the top of the drain. The receptor floor slopes 1/8 to 1/2 inch per foot to the drain, and the nailing flange rises at least 1 inch above the receptor sides.

2025 California Plumbing Code, Chapter 4 (Plumbing Fixtures and Fixture Fittings) · Applies to: Homes and commercial buildings

Section through a shower receptor showing the curb at least 1 inch lower than the sides, 2 to 9 inches above the drain, a nailing flange 1 inch above the sides, and the 1/8 to 1/2 inch per foot floor slope.
Curb 1 in below the sides, 2 to 9 in above the drain, flange 1 in above the sides, floor sloped 1/8 to 1/2 in per ft. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Where a shower receptor has a finished dam, curb or threshold, it has to be not less than 1 inch lower than the sides and back of the receptor. Measured from the top of the dam or threshold to the top of the drain, it can't be less than 2 inches or more than 9 inches.

Each receptor needs a nailing flange, either built in or field installed per the manufacturer's instructions. The flange is watertight and extends vertically not less than 1 inch above the top of the sides of the receptor. The finished floor slopes uniformly from the sides to the drain, not less than 1/8 inch per foot and not more than 1/2 inch per foot.

The threshold has to be wide enough for a door of at least 22 inches, and the door has to open so there's at least a 22 inch unobstructed opening for egress. A shower without a threshold makes the floor space in the same room a wet location under the California Building Code, California Residential Code and California Electrical Code.

There are exceptions for showers under Section 403.2, and for flanges: a cast-iron receptor flange, and a sealing flange that isn't used to secure the receptor, are each not less than 0.3 inch high.

On the job

  • Build the curb height from the top of the drain, not from the bathroom floor. That's the measurement the code uses.
  • Check the slope with a level and a ruler at the pan test. The code range is 1/8 to 1/2 inch per foot, and a flat spot holds water.
  • On a curbless shower, tell the electrician and the builder before rough-in. The floor space in that room is a wet location, so light and receptacle locations follow the wet-location rules.

The inspector and your city's adopted edition have the final word.