The rule
Where a shower receptor has a finished dam, curb or threshold, it has to be not less than 1 inch lower than the sides and back of the receptor. Measured from the top of the dam or threshold to the top of the drain, it can't be less than 2 inches or more than 9 inches.
Each receptor needs a nailing flange, either built in or field installed per the manufacturer's instructions. The flange is watertight and extends vertically not less than 1 inch above the top of the sides of the receptor. The finished floor slopes uniformly from the sides to the drain, not less than 1/8 inch per foot and not more than 1/2 inch per foot.
The threshold has to be wide enough for a door of at least 22 inches, and the door has to open so there's at least a 22 inch unobstructed opening for egress. A shower without a threshold makes the floor space in the same room a wet location under the California Building Code, California Residential Code and California Electrical Code.
There are exceptions for showers under Section 403.2, and for flanges: a cast-iron receptor flange, and a sealing flange that isn't used to secure the receptor, are each not less than 0.3 inch high.
On the job
- Build the curb height from the top of the drain, not from the bathroom floor. That's the measurement the code uses.
- Check the slope with a level and a ruler at the pan test. The code range is 1/8 to 1/2 inch per foot, and a flat spot holds water.
- On a curbless shower, tell the electrician and the builder before rough-in. The floor space in that room is a wet location, so light and receptacle locations follow the wet-location rules.
The inspector and your city's adopted edition have the final word.