The rule
Tubs and whirlpool tubs go in per the manufacturer's installation instructions. The access opening has to be a size and shape that lets you remove and replace the circulation pump.
Where the pump is reached from a crawl space, its access has to be not more than 20 feet from an access door, trap door or crawl hole.
The circulation pump is located above the crown weir of the trap, and the pump and circulation piping self-drain to cut down on retained water.
Suction fittings on whirlpool tubs comply with ASME A112.19.7/CSA B45.10, and flexible PVC hoses or tubing used on whirlpool circulation or pneumatic systems comply with IAPMO/ANSI Z1033.
On the job
- Set the pump height from the trap, not from the tub deck. The pump has to be above the crown weir of the trap.
- Check the access opening against the pump's actual size. If the pump can't come out through the opening, it doesn't meet the rule.
- In a crawl space, measure the path from the nearest access door or crawl hole to the pump. It has to be within 20 feet.
- Plan the access before drywall goes up: a panel in the adjacent closet, vanity or hall wall costs far less than cutting one in later.
The inspector and your city's adopted edition have the final word.