CPC 507.25 · Water heaters

Access and working space around a water heater

Every appliance has to be placed so it can be repaired or replaced, and unless something else is specified you keep 30 inches of working space in depth, width and height.

2025 California Plumbing Code, Chapter 5 (Water Heaters) · Applies to: Homes and commercial buildings

A water heater in an alcove with a dashed 30 inch deep, 30 inch wide and 30 inch high working space in front of its controls.
Keep at least 30 inches of depth, width and height clear for service, unless something else is specified. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Appliances have to be located so people can get to them for repair or replacement. That means clearance to take the appliance out, clean it, replace parts such as controls and vent connections, and adjust burners and pilots.

Unless something else is specified, the working space is at least 30 inches deep, wide and tall. In practice it's measured in front of the part you service, so the controls and burner access panel aren't facing a wall.

For attic installations, the passageway and working area follow Section 508.4 instead.

On the job

  • Set the heater so the controls face the open side, then check you can reach the drain, the shutoffs and the relief valve without moving anything.
  • Don't shelve in front of the heater. Storage in the working space is a common correction.
  • The manufacturer's instructions often ask for more clearance than the code's floor. Use whichever is greater.

The inspector and your city's adopted edition have the final word.