Home › Code Library › CPC 509.6

CPC 509.6 · Water heaters

Gas vent (Type B) termination above the roof

A Type B gas vent ends at least 5 feet above the draft hood or flue collar. Through the roof, a vent of 12 inches or less and at least 8 feet from a wall rises to the Table 509.6.1 height (1 foot for a flat to 6/12 roof). Closer to a wall, or larger, it goes at least 2 feet above the roof and above anything within 10 feet.

2025 California Plumbing Code, Chapter 5 (Water Heaters) · Applies to: Homes and commercial buildings

A roof section with a Type B vent: 5 feet above the draft hood, a roof-pitch height table for vents 8 feet or more from a wall, and the 2 foot and 10 foot rule for vents closer to a wall.
5 feet above the draft hood; roof-pitch height when 8 feet or more from a wall; otherwise 2 feet above the roof and anything within 10 feet. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Install gas vents per the manufacturer's instructions. Where a Type B or Type L vent serves a draft-hood water heater, it ends at least 5 feet in vertical height above the highest connected draft hood or flue collar.

At the roof there are two cases. A vent that's 12 inches or less in size and at least 8 feet from a vertical wall or similar obstruction ends above the roof at the height in Table 509.6.1, which depends on roof pitch: 1 foot for flat to 6/12, 1.25 feet for over 6/12 to 7/12, 1.5 feet for over 7/12 to 8/12, and 2 feet for over 8/12 to 9/12, rising with steeper roofs. A vent over 12 inches, or less than 8 feet from a wall, has to end at least 2 feet above where it passes through the roof and at least 2 feet above any part of the building within 10 feet horizontally.

The vent goes through the roof flashing, jack or thimble and ends with a listed cap or listed roof assembly. It can't end adjacent to a wall or below eaves or parapets, and it has to be at least 3 feet above a forced air inlet within 10 feet. Where it passes through insulation, a steel shield of 26 gauge or heavier goes between the vent and the insulation and extends at least 2 inches above it. Screws and rivets can't poke through the inner wall of double-wall vent, except at the transition from the draft hood or connector.

On the job

  • Find the roof pitch before you cut: pitch sets the height, and the 5 foot above-the-collar rule can control on a tall vent run.
  • Check the distance to the nearest wall, dormer or higher roof. Inside 8 feet it's the 2-foot, 10-foot rule that applies.
  • Look for forced air inlets (a furnace or air intake) within 10 feet of the cap. They need the 3 foot rise.

The inspector and your city's adopted edition have the final word.