The rule
The clearances for through-the-wall direct-vent and non-direct-vent terminals come from Table 509.8.1 and its figure. The combustion air intake of a direct-vent appliance is exempt from the table.
A few rows matter on most jobs. Above finished grade, a veranda, porch, deck or balcony: 12 inches. To an openable window or door, a direct-vent terminal needs 6 inches for appliances up to 10,000 Btu/hr, 9 inches above that up to 50,000, and 12 inches above that up to 150,000. A non-direct-vent terminal needs 4 feet below or to the side of the opening, or 1 foot above it. Clearance to a mechanical air supply inlet is 10 feet horizontally or 3 feet above. Above a paved sidewalk or driveway on public property it's 7 feet. Under a veranda, porch, deck or balcony it's 12 inches, and only where the space beneath is open on at least two sides.
Where a vent or combustion air intake pipe goes through an outside wall, the gap around it has to be permanently sealed with approved materials so combustion products can't get into the building. Category IV vents that discharge perpendicular to an adjacent wall go at least 10 feet horizontally from an operable opening in an adjacent building, unless the terminal is 2 feet or more above, or 25 feet or more below, that opening.
On the job
- Walk the exterior wall before you core. Windows, doors, soffit vents, outside corners, a neighbor's window, and a dryer or air intake all count.
- Seal the annular space as part of the install, with an approved material, and make sure it stays sealed after the siding or trim goes on.
- For a power-vent or direct-vent heater, the manufacturer's clearances can be larger than the table's. Follow the greater.
The inspector and your city's adopted edition have the final word.