CPC 610.12 · Water supply and distribution

Water velocity limits: 8 ft/s cold, 5 ft/s hot

Copper tube and fitting systems can't exceed 8 feet per second in cold water or 5 feet per second in hot water. The same limits apply through copper fittings in tubing other than copper. Appendix A gives the other velocity limits.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

Two pipe runs compared: cold water limited to 8 feet per second and hot water limited to 5 feet per second in copper tube and fittings.
Copper tube and fittings: 8 ft/s cold, 5 ft/s hot. The same limits apply through copper fittings on other tubing. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

The code caps how fast water can move in the pipe. In copper and copper alloy tube and fitting systems, the maximum is 8 feet per second in cold water and 5 feet per second in hot water.

The same 8 and 5 feet per second limits apply to velocity through copper fittings used with tubing that isn't copper, such as copper fittings on PEX or CPVC. The limits are in this section or Appendix A.

Section 610.1 repeats the point: pipes are designed so the maximum velocities allowed by the code and the standard aren't exceeded.

On the job

  • Check velocity on high-flow runs, such as a long run feeding a tankless heater or a branch with several fixtures, before settling for the smallest pipe that satisfies the fixture units.
  • Hot water gets the lower limit. A hot water run can pass the cold water number and still be over its own.
  • If the numbers don't work, the fix is usually a bigger pipe or a shorter, split run. Check the manufacturer's flow charts or Appendix A.

The inspector and your city's adopted edition have the final word.