CPC 610.4 · Water supply and distribution

Sizing water pipe and meter with Table 610.4

Table 610.4 sizes the meter and building supply from four inputs: available pressure, developed length to the farthest outlet, elevation of the highest outlet, and total fixture units from Table 610.3. Find the pressure group, pick the length column, go down to a fixture unit value at or above your total, then read the pipe sizes. No building supply is smaller than 3/4 inch.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

Six steps for sizing a meter and building supply with Table 610.4 and an excerpt of the 30 to 45 psi group with the 100 foot column highlighted.
Example only: 45 psi available, 100 feet, 30 fixture units: a 3/4 inch meter with 1-1/4 inch supply carries 28 (too small), so use the 1 inch meter with 1-1/4 inch supply (38). Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Gather four things first: total fixture units for the fixtures being installed (Table 610.3), the developed length of supply pipe from the meter to the most remote outlet, the elevation difference between the meter and the highest outlet, and the pressure at the meter. Where street pressure swings during the day, design for the minimum pressure available.

Then work the table. Start with the available pressure at the meter, and add or subtract 1/2 psi for each foot of elevation difference between the meter and the highest outlet. Use the pressure range group that result falls into (30 to 45 psi, 46 to 60 psi, or over 60 psi). Pick the length column that equals or exceeds your developed length. Go down that column to a fixture unit value at or above your total. The two left-hand columns of that row give the meter size and the building supply size. No building supply pipe is smaller than 3/4 inch.

Branches use the same steps with the fixture units served by that branch, and no branch is sized for more than the system's total demand. Where a regulator is installed, the pipe is sized on 80 percent of the reduced pressure (608.2).

Table 610.4 is one route. The code also allows sizing by the Appendix A procedure, and Appendices C and M give alternatives. Listed parallel (home-run) systems follow their listing, and velocities still can't exceed the code limits (610.12).

On the job

  • Write down your four inputs before you open the table. For example (made-up numbers): 55 psi at the meter and the highest outlet 20 feet above it gives 55 minus 10, or 45 psi, so use the 30 to 45 psi group. With 100 feet of developed length and 30 fixture units, the 3/4 inch meter with 1-1/4 inch supply only reaches 28, so step up to a 1 inch meter with 1-1/4 inch supply, which is good for 38.
  • Always read the length column that's equal to or longer than your run, never a shorter one.
  • Table 610.3 gives the fixture units and the minimum branch size for each fixture. It also lists the loads on the cold supply, and the hot and cold shares can each be taken as three-quarters of the listed total.

The inspector and your city's adopted edition have the final word.