CPC 707.8 · Sanitary drainage and sewers

Cleanout access and clearances

A cleanout has to be above grade (or under an approved cover plate) and readily accessible, with 18 by 18 inches of clear space in front of it on pipe 2 inches or smaller and 24 by 24 inches on larger pipe. Under-floor cleanouts can't be more than 5 feet from the access opening.

2025 California Plumbing Code, Chapter 7 (Sanitary Drainage) · Applies to: Homes and commercial buildings

Front view showing 18 by 18 inch clearance for cleanouts on pipe 2 inches or smaller and 24 by 24 inches for larger pipe, and a crawl space section showing the 5 foot limit and 30 inch clearance.
Keep 18 by 18 inches clear on small pipe and 24 by 24 on larger; under a floor, stay within 5 feet of the access opening. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Each cleanout has to be above grade, readily accessible, and located where it can do its job. The exception is a cleanout under an approved cover plate, which still has to give you the same clearances and access.

In front of a cleanout on pipe 2 inches or smaller you need at least 18 inches by 18 inches clear. On pipe larger than 2 inches it's 24 by 24 inches.

Under-floor cleanouts have special rules. If there's less than 18 inches of vertical clearance overall (counting ducts, beams and piping), the cleanout has to be extended up to or above the finished floor, or outside the building. You also need 30 inches of horizontal clearance from the means of access, and no under-floor cleanout can be more than 5 feet from an access door, trap door or crawl hole.

On the job

  • Plan clearance before the finish crews arrive. A cleanout behind a vanity, a cabinet or a water heater doesn't have the clearance, and moving it later means opening walls.
  • In a crawl space, look at where the access hole is before you pick the cleanout spot. If the 5 foot limit would be exceeded, extend the cleanout toward the opening.
  • Where a cleanout comes up through a finished floor, use an approved cover plate so it stays reachable, and use a load-rated cover where it will see traffic.

The inspector and your city's adopted edition have the final word.