The rule
When a fixture is below the sewer's crown level, it drains by gravity into a watertight sump, and an ejector or pump lifts the waste up to the building drain or sewer (Section 710.2). Section 710.3 sets the minimum for the pump when it handles water closets or urinals.
It has to have a discharge capacity of at least 20 gpm. In a single dwelling unit it has to pass a 1-1/2 inch solid ball and the discharge pipe has to be at least 2 inches. In other than single dwelling units it has to pass a 2 inch solid ball and the discharge pipe has to be at least 3 inches. Each discharge line needs a backwater valve and a gate valve.
Section 710.4 adds that the discharge line is pressure-rated pipe, the gate or ball valve sits on the discharge side of the backwater or check valve, and a connection to a horizontal gravity line goes in from the top through a wye. For sizing the line that receives it, 2 fixture units count for each gallon per minute of pump flow (Section 710.5).
On the job
- Check valve first, then gate valve, in the flow direction, both accessible. Plan the access cover or pit before the slab goes in (Section 710.6).
- The sump needs a vent that extends through the roof or ties to other vents, plus a watertight bolted cover. Section 710.10 has the sizes and the details.
- Public-use occupancies need dual pumps and an audio and visual alarm (Section 710.9), so confirm the use group before you price the system.
The inspector and your city's adopted edition have the final word.