CPC 906.1 · Vents

Roof vent: 6 inches above the roof, 1 foot from walls

A vent extends through its flashing and ends vertically at least 6 inches above the roof and at least 1 foot from a vertical surface. ABS or PVC left in the sun gets a water-based synthetic latex paint.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Homes and commercial buildings

A vent pipe through a roof flashing ending 6 inches above the roof and 1 foot from a vertical wall.
Through the flashing, vertical, at least 6 in above the roof and 1 ft from any vertical surface. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

The vent goes through the roof in a flashing and ends vertically, open to the air. It has to stick up at least 6 inches above the roof and be at least 1 foot from any vertical surface, like a parapet, dormer wall or chimney.

ABS and PVC vent pipe exposed to sunlight has to be protected with water-based synthetic latex paint. It keeps the UV from breaking down the plastic over the years.

Where a vent ends relative to windows, doors and property lines is a separate rule in Section 906.2, and flashing details are in Section 906.5.

On the job

  • Measure the 6 inches from the roof surface at the pipe.
  • Keep the vent off a parapet or a wall face. Inspectors check the 1 foot from the nearest vertical surface, including a dormer wall.
  • Paint exposed plastic before the final. Use water-based latex, not an oil paint or solvent-based coating.

The inspector and your city's adopted edition have the final word.