CPC 906.2 · Vents

Vent clearance from windows, doors and lot lines

A vent has to end at least 10 feet from, or at least 3 feet above, an openable window, door, opening, air intake or vent shaft, and at least 3 feet in every direction from a lot line (a street or alley doesn't count).

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Homes and commercial buildings

A roof beside a window showing a vent too close and too low, a vent 3 feet above the window top, and a vent 10 feet away, plus a lot-line panel showing 3 feet in every direction.
Either 10 ft away or 3 ft above an openable window, door, opening or air intake; 3 ft in every direction from a lot line. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Sewer gas shouldn't blow into a window or an air intake. So the vent opening has to be either at least 10 feet away from an openable window, door, opening, air intake or vent shaft, or at least 3 feet above it.

Lot lines get their own distance: at least 3 feet in every direction from a lot line. Streets and alleys are the exception, so you don't measure from those.

Either clearance is measured to the vent's opening, not to the pipe where it comes through the roof.

On the job

  • Check the neighbor's side too. A vent close to a side lot line, or just under a neighbor's openable window, is the one that gets flagged.
  • On a tight lot, the easiest fix is usually raising the vent so its top is 3 feet above the window or intake. Make sure the added height still meets the roof rules in Section 906.1.
  • Check where the HVAC outside-air intakes and bath fan ducts land before you pick the vent location.

The inspector and your city's adopted edition have the final word.