CPC 905.6 · Vents

Two fixtures on a common vertical pipe

Two fixtures can share a common vertical pipe when each wastes separately into an approved double fitting with its inlets at the same level.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Homes and commercial buildings

Two lavatories on opposite sides of a wall, each with its own trap, wasting into one double fitting at the same level on a common vertical pipe that continues up as a vent.
Each fixture wastes separately into a double fitting with both inlets at the same level, and the pipe above serves as their common vent. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

A common vent lets one vertical pipe serve two fixtures. Each fixture wastes into its own side of a double fitting, such as a double sanitary tee, and both inlets sit at the same level.

Because the pipe is common, it has to be sized for both fixtures, and the vent above it still has to meet the rest of Chapter 9.

It's a way to vent two fixtures set back to back on opposite sides of a wall, such as two lavatories, with one vertical pipe.

On the job

  • Use a real double fitting with both inlets at the same level, not two separate tees stacked. Inspectors look for that.
  • Back-to-back fixtures in a shared wall are the typical use. Check the wall depth before you commit; a double fitting needs room.
  • A common vertical pipe still has to be sized for the fixtures it serves, and the vent above it has to meet the rest of Chapter 9.

The inspector and your city's adopted edition have the final word.