The rule
Drainage stacks that extend 10 or more stories get a parallel vent stack, and that vent stack is tied to the drainage stack by a yoke vent at each fifth floor, counting down from the top (Section 907.1). The yoke vent is that connecting pipe.
The yoke connects to the vent stack at least 42 inches above the floor level.
At the drainage stack the yoke connects with a wye-branch fitting placed below the lowest drainage branch connection serving that floor, so the vent picks up the stack under the branches.
On the job
- Yoke vents show up in tall buildings. Mark the yoke elevations on the riser diagram.
- Use a wye on the drainage stack, with the branch angled up. A sanitary tee aimed the wrong way is a correction.
- The yoke is at least as big as the smaller of the drainage and vent stacks (Section 907.1).