CPC 907.2 · Vents

Yoke vent: 42 inches above the floor

A yoke vent ties a drainage stack to its parallel vent stack. It connects to the vent stack at least 42 inches above the floor and to the drainage stack with a wye below the lowest branch serving that floor.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Commercial buildings

A drainage stack and a parallel vent stack joined by a yoke vent that leaves the drainage stack through a wye below the lowest branch and meets the vent stack at least 42 inches above the floor.
Yoke vent: wye below the lowest branch on the drainage stack, tied to the vent stack at least 42 in above the floor. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Drainage stacks that extend 10 or more stories get a parallel vent stack, and that vent stack is tied to the drainage stack by a yoke vent at each fifth floor, counting down from the top (Section 907.1). The yoke vent is that connecting pipe.

The yoke connects to the vent stack at least 42 inches above the floor level.

At the drainage stack the yoke connects with a wye-branch fitting placed below the lowest drainage branch connection serving that floor, so the vent picks up the stack under the branches.

On the job

  • Yoke vents show up in tall buildings. Mark the yoke elevations on the riser diagram.
  • Use a wye on the drainage stack, with the branch angled up. A sanitary tee aimed the wrong way is a correction.
  • The yoke is at least as big as the smaller of the drainage and vent stacks (Section 907.1).

The inspector and your city's adopted edition have the final word.