The rule
This section is a pointer. It doesn't describe the firestop method. It tells you that any pipe penetrating a rated assembly gets protected per the California Building Code or California Residential Code. The rated assemblies are walls, partitions, floors, floor/ceiling assemblies, roof/ceiling assemblies and shaft enclosures.
The plumbing code's own firestop chapter (Chapter 14, with the applicability rule in 1401.1) covers the systems and materials, and 1403.1 says to install them per the manufacturer's instructions.
In practice this means a listed firestop system matched to the rated assembly, the pipe material and the pipe size. A tube of caulk isn't a firestop system on its own.
On the job
- Find out early which walls and floors are rated. On plans they're marked, and a rated wall between an attached garage and the house, or between units, is the common one.
- Pick a listed system that matches the assembly and the pipe (plastic and metal pipe are treated differently), and follow its installation instructions to the letter.
- Firestopping is usually inspected as its own step before the wall closes, so leave it exposed until it's signed off.
The inspector and your city's adopted edition have the final word.