The rule
When you borrow volume from the next room, you connect the spaces with permanent openings. For spaces on the same story, one opening starts within 12 inches of the top of the enclosure and one starts within 12 inches of the bottom, and each has to have at least 1 square inch of free area per 1000 Btu/h of the total input of all appliances in the space. Neither can be smaller than 100 square inches, and the smallest dimension of any opening is 3 inches.
Free area means the actual open area after any louver, grille or screen takes its share. That's why a louvered door's overall size isn't its free area, and why you check the maker's free area rating.
A water heater at or under 100,000 Btu/h lands on the 100 square inch minimum for each opening. Bigger input scales up at 1 square inch per 1000 Btu/h.
When the spaces are on different stories, the openings can be in doors or floors, and their total minimum free area is 2 square inches per 1000 Btu/h of total appliance input.
On the job
- Measure the net free area on louvered or grilled doors. A door vent that looks big can come in well under the minimum.
- Keep openings permanent. No dampers, no weather stripping the gap closed, and no stored boxes blocking them.
- The top and bottom openings do different jobs: the bottom one feeds air in and the top one relieves warm air. Both are required, and they have to be where the code puts them.
The inspector and your city's adopted edition have the final word.