The rule
Two permanent openings: one starts within 12 inches of the top of the enclosure and one within 12 inches of the bottom. They connect to the outdoors directly or through ducts, or to spaces that freely communicate with the outdoors. With direct openings or vertical ducts, each is at least 1 square inch per 4000 Btu/h of total input. With horizontal ducts, each is at least 1 square inch per 2000 Btu/h.
One permanent opening: it starts within 12 inches of the top of the enclosure. The appliance needs at least 1 inch of clearance on the sides and back and 6 inches in front. The opening has to be at least 1 square inch per 3000 Btu/h of total input, and at least the combined area of all the vent connectors in the space.
Either way, no dimension of an air opening is under 3 inches. When you combine indoor and outdoor air, Section 506.5 gives the reduction math.
On the job
- Ducts count as the longer path, which is why horizontal ducts need double the area of direct openings. Pick the right line before you size the grille.
- The one-opening method has clearance conditions built in. A tight closet that can't give 1 inch on the sides and back and 6 inches in front can't use it.
- Put the exterior openings where leaves and debris won't clog them, and count the screen's effect on free area when you size them.
The inspector and your city's adopted edition have the final word.