Home › Code Library › CPC 604.13

CPC 604.13 · Water heaters

Water heater connectors and PEX near the heater

Flexible water heater connectors have to meet ASME A112.18.6/CSA B125.6, copper and stainless flexible connectors can't be longer than 24 inches, and PEX or PE-RT tubing can't be used within the first 18 inches of piping connected to the heater.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

Water heater with flexible connectors no longer than 24 inches and the first 18 inches of connected piping kept metal before PEX or PE-RT tubing begins.
Flexible metal connectors: 24 inches maximum. No PEX, PEX-AL-PEX, PE-AL-PE or PE-RT within the first 18 inches of connected piping. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

The flexible connectors used on water heaters (flexible copper or stainless, reinforced flexible, braided stainless, or polymer braided with an EPDM core) have to comply with ASME A112.18.6/CSA B125.6. Flexible copper, copper alloy or stainless connectors can't be longer than 24 inches.

Tubing like PEX, PEX-AL-PEX, PE-AL-PE and PE-RT can't be installed within the first 18 inches of piping connected to a water heater. Use metal for that first stretch, then transition to the plastic.

In California, PEX-AL-PEX isn't adopted for potable water supply and distribution, so that material isn't an option on ordinary jobs.

On the job

  • Measure the 18 inches from the heater's own inlet and outlet connections. If the plastic starts inside that distance, it has to be moved out.
  • Pick a connector length that doesn't need to kink or loop. Anything over 24 inches in flexible copper or stainless is out.
  • The cold supply to the heater needs a fullway valve at or near the heater (606.2), so plan the metal stub-out with the valve in mind.

The inspector and your city's adopted edition have the final word.