The rule
Join PEX only with the tubing manufacturer's installation instructions in hand. Fittings have to meet the standards in Table 604.1, and PEX tubing that meets ASTM F876 is marked with the fitting standard the manufacturer specifies for it.
Brass fittings used with PEX have to meet or exceed NSF/ANSI 14, so they don't dezincify or stress crack. Mechanical joints follow the manufacturer's instructions, and push-fit fittings, whether removable or not, have to comply with ASSE 1061.
California adds a UV rule: all PEX pipe installed has to provide at least 30-day UV protection. For hospitals and other OSHPD work, PEX can't be used in any way that would break another provision of the California Building Standards Code.
On the job
- Use the fitting system the tubing maker specifies for that tubing. Mixing brands can put the joint outside what the tubing is listed for.
- Read the UV rating printed on the tubing and keep it covered on the job site. Check the manufacturer's limits before leaving rolls out in the sun.
- New PEX in a California home also has the flush-and-tag rule (604.1.2), so plan the fill before the final.
The inspector and your city's adopted edition have the final word.