CPC 608.3 · Water heaters

Expansion tanks and combination T&P valves

A water system with a check valve, backflow preventer or other normally closed device that traps building pressure needs an approved expansion tank on the building side of that device. A storage water heater needs a combination T&P valve with a drain that meets 608.5.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

Water service through a backflow preventer into the building with an expansion tank on the building side and a storage water heater with a T&P valve and drain.
Expansion tank on the building side of the check valve or backflow preventer. Storage water heater gets a T&P valve with a drain (608.5). Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Heating water makes it expand. If the system has a check valve, backflow preventer or other normally closed device that keeps the pressure from backing into the water main, the expansion has nowhere to go. The code requires an approved, listed, adequately sized expansion tank (or another approved device that does the same job) whatever type of water heater is used. Prepressurized tanks have to comply with IAPMO/ANSI Z1088.

The tank goes on the building side of the check valve, backflow preventer or other device, and it has to be sized, securely fastened to the structure, and installed per the manufacturer's instructions.

A system with a storage water heater also needs an approved, listed, adequately sized combination temperature and pressure-relief valve (T&P), installed on the heater in an approved location based on its listing and the manufacturer's instructions. The T&P valve needs a drain that meets 608.5. Listed nonstorage instantaneous heaters with an inside diameter of not more than 3 inches are excepted from the T&P requirement, and an expansion tank isn't required for an instantaneous non-storage water heater.

On the job

  • A dripping T&P valve on a heater with a new PRV, meter backflow device or dual check is often a missing or dead expansion tank. Check the tank's air charge first.
  • Support the tank so its weight isn't hanging on the pipe. The code says securely fastened to the structure.
  • The T&P discharge has its own rules (608.5). Run it before you call the water heater done.

The inspector and your city's adopted edition have the final word.