CPC 604.3 · Water supply and distribution

Copper water tube: Type L minimum, Type M in two places

Copper water tube has to be at least Type L weight. Type M is allowed only where the piping is aboveground in or on a building, or underground outside of structures. Hard-drawn tube is color-marked: green K, blue L, red M.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

Cutaway of a building and yard showing Type M allowed aboveground in the building and underground outside, and Type L required for copper that is underground inside the building.
Type M: aboveground in or on a building, or underground outside of structures. Under the slab and other underground runs inside the building: Type L or heavier. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Type L is the minimum weight (wall thickness) for copper or copper alloy tube in water piping. Type M is thinner, and the code allows it in two situations: aboveground in or on a building, or underground outside of structures.

Read together, that means copper that's underground inside the building, like water piping under a slab, has to be Type L or heavier. Type M stays in the walls, attic and above-grade runs, and in yard lines outside.

Hard-drawn tube carries the incised marking and a color: Type K is green, Type L is blue, Type M is red.

On the job

  • Check the color stripe when copper arrives. Red is Type M, which can't go under the slab.
  • Under-slab runs also have their own rules for joints (609.3), so plan the layout to keep joints out of the slab.
  • Yard lines outside the structure are one of the two places Type M is allowed. Once the line comes up through the foundation, the Type L rule for underground piping inside the building takes over.

The inspector and your city's adopted edition have the final word.