The rule
Temperature, pressure and vacuum relief devices, or combinations of them, and automatic gas shutoff devices are installed according to their listings and the manufacturer's installation instructions.
No shutoff valve of any kind can sit between the relief valve and the water heater, or on the discharge pipe between the valve and the open air. If the valve could ever be closed, it can't do its job.
Size the valve by capacity, not by thread size. The hourly Btu discharge capacity, or the rated steam relief capacity, has to be at least the input rating of the water heater. The valve's rating is on the valve, and the heater's input is on its data plate.
The discharge piping from the valve follows Section 608.5: full size, no valves, no traps, drained by gravity to a visible termination.
On the job
- When you replace a T&P, match the valve to the heater's input and to the tank's listed tapping. Don't reuse a valve rated for a smaller heater.
- Don't thread a ball valve, a cap or an adapter into the relief outlet. The only fitting that belongs there is the discharge pipe.
- Check the sensing end of the T&P is in the tank's designated location per the heater's instructions. A valve that isn't in the water can't sense the temperature.
The inspector and your city's adopted edition have the final word.