The rule
"Within a building" here means within the fixed limits of the building foundation. Water piping in or under a concrete slab resting on the ground inside those limits follows two rules.
Ferrous (iron or steel) piping has to have a machine-applied protective coating of an approved type that meets recognized standards. Field wrapping is allowed only on the short sections and fittings that had to be stripped for threading. Zinc coating (galvanizing) isn't adequate protection. Approved nonferrous piping isn't required to be wrapped.
Copper or copper alloy tubing goes in without joints where possible. Where joints are permitted, they're brazed, and the fittings are wrought copper.
On the job
- Run copper under the slab in one piece wherever the layout allows. Every joint you avoid is one you can't leak at.
- If a joint has to be there, braze it with a wrought copper fitting. Solder and cast fittings aren't what this section calls for.
- Check the pipe type for this location, too: copper under the slab inside the building is Type L or heavier (604.3).
The inspector and your city's adopted edition have the final word.