The rule
An air test attaches an air compressor testing apparatus to a suitable opening on the drain and vent system, with all other inlets and outlets closed. Air goes in until the gauge shows a uniform 5 psi, or enough pressure to balance a column of mercury 10 inches high.
Then the pressure has to hold, without adding any more air, for at least 15 minutes.
Section 712.1 sets one limit up front: plastic pipe shall not be tested with air. For ABS and PVC drain and vent, the water test (Section 712.2) is the test that applies. That section also lets the Authority Having Jurisdiction require removal of cleanouts to confirm the pressure reached all parts of the system.
On the job
- Use a gauge you can read at 5 psi. A pressure gauge built for much higher pressures won't show a slow drop.
- Close every opening. A single open trap arm or an unplugged vent stub drops the pressure and you'll waste time hunting a leak that's just an open pipe.
- Keep people away from the test. Compressed air in a closed system is stored energy, and a plug that lets go is a hazard.
The inspector and your city's adopted edition have the final word.