CPC 712.3 · Sanitary drainage and sewers

Air test for drain and vent piping

An air test closes every other inlet and outlet and forces air in until the gauge reads a uniform 5 psi, or enough to balance 10 inches of mercury. The pressure has to hold with no added air for at least 15 minutes. Plastic pipe can't be air tested.

2025 California Plumbing Code, Chapter 7 (Sanitary Drainage) · Applies to: Homes and commercial buildings

A drain and vent system with a compressor and gauge at one opening, every other opening plugged, reading 5 psi, with a note that plastic pipe is not air tested.
Seal every other opening, bring the gauge to a uniform 5 psi, and hold it 15 minutes with no added air. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

An air test attaches an air compressor testing apparatus to a suitable opening on the drain and vent system, with all other inlets and outlets closed. Air goes in until the gauge shows a uniform 5 psi, or enough pressure to balance a column of mercury 10 inches high.

Then the pressure has to hold, without adding any more air, for at least 15 minutes.

Section 712.1 sets one limit up front: plastic pipe shall not be tested with air. For ABS and PVC drain and vent, the water test (Section 712.2) is the test that applies. That section also lets the Authority Having Jurisdiction require removal of cleanouts to confirm the pressure reached all parts of the system.

On the job

  • Use a gauge you can read at 5 psi. A pressure gauge built for much higher pressures won't show a slow drop.
  • Close every opening. A single open trap arm or an unplugged vent stub drops the pressure and you'll waste time hunting a leak that's just an open pipe.
  • Keep people away from the test. Compressed air in a closed system is stored energy, and a plug that lets go is a hazard.

The inspector and your city's adopted edition have the final word.