CPC 910.3 · Vents

Combination waste and vent: vent size and the 15 foot branch

A combination waste and vent system needs a vent with at least half the cross-sectional area of the drain it serves, connected downstream of the uppermost fixture. A branch longer than 15 feet needs its own separate vent. Plans must be approved before any of it is installed.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Homes and commercial buildings

Three fixtures with short tailpieces draining into an oversized horizontal waste pipe, with a vent connected downstream of the uppermost fixture and a note that a branch over 15 feet needs a separate vent.
Vent downstream of the uppermost fixture, at least half the drain's area, and a separate vent for any branch over 15 ft. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

A combination waste and vent system uses an oversized drain as its own vent. It's allowed only where the structure keeps you from installing a conventional system, and the construction documents have to be approved by the authority having jurisdiction before you install any part of it.

The system still needs a real vent, or vents, enough to keep air moving. The vent's area has to be at least half the inside cross-sectional area of the drain pipe it serves, and it connects downstream of the uppermost fixture.

A branch longer than 15 feet is vented separately in an approved way. You can't just keep extending the oversized drain.

On the job

  • Get the plans approved first. Roughing in a combination waste and vent and asking afterward is the way to tear it out.
  • Half the area isn't half the diameter. Do the area math, or ask your inspector how they want the vent sized, before you order pipe.
  • Check the length of each branch. Once one passes 15 feet, plan the extra vent.

The inspector and your city's adopted edition have the final word.