The rule
An island has no wall to carry a vent up, so the code lets you loop the vent. The vent extends as high as possible, no lower than the drainboard height, then returns down and connects to the horizontal sink drain just downstream of the vertical fixture drain with a wye.
A foot vent takes off the vertical vent with a wye just below the floor and runs to the nearest partition, then up through the roof. It can also tie into other vents at least 6 inches above the flood-level rim of the fixtures served. Below the floor use drainage fittings and slope the foot vent at least 1/4 inch per foot back to the drain. The foot vent needs an accessible cleanout in its vertical part.
The return bend under the drainboard is either one piece or a 45 degree, a 90 degree and a 45 degree elbow, in that order. The island sink drain upstream of the returned vent can't serve any other fixtures. Pipe sizing follows the rest of the code.
On the job
- Check the cabinet first. The return vent and the trap have to be roughed in above the floor in the island base, so plan the cabinet depth with the cabinet maker.
- The cleanout in the foot vent has to be reachable once the island is finished. Put it where you can get a tool to it.
- Slope the foot vent back toward the drain and keep it free of dips.
The inspector and your city's adopted edition have the final word.