The rule
Public-use lavatories can't deliver water hotter than 120°F (49°C). It's scald protection for the public.
There are two ways to meet it. One is a limiting device that conforms to ASSE 1070 (also marked ASME A112.1070/CSA B125.70). The other is a water heater that conforms to ASSE 1084.
Section 407.4 is a separate rule for lavatories that serve the transient public, such as those in service stations, train stations, airports, restaurants and convention halls. Those get self-closing or metering faucets.
On the job
- Check the temperature at the faucet with a thermometer after you set the device, not only at the heater. Run the water long enough to see the peak.
- Keep the device's model and its ASSE marking handy for the inspector.
- Tell the building's maintenance contact where the limiting device is. If someone cranks it back up later, the rule is broken.
The inspector and your city's adopted edition have the final word.