The rule
Showers and tub-shower combinations get an individual control valve of the pressure balance, thermostatic, or combination pressure balance/thermostatic type. It's installed at the point of use, gives scald and thermal shock protection at the rated flow of the installed showerhead, and complies with ASSE 1016 (ASME A112.1016/CSA B125.16) or ASME A112.18.1/CSA B125.1.
The water temperature at an individual showerhead is limited to 120°F (49°C). The code gives two ways. One is an ASSE 1016 valve that's either field-adjusted to the maximum temperature or has its handle position, stop or temperature limiting control set to that maximum following the manufacturer's instructions. The other, for gang showers on a single supply pipe, is an ASSE 1069 mixing valve field-adjusted to the maximum.
Gang showers supplied by one temperature-controlled pipe are controlled by an ASSE 1069 mixing valve. Temperature-actuated flow-reduction devices (ASSE 1062) can't stand in for the balanced pressure, thermostatic or combination shower valve, or for bathtub and whirlpool temperature-limiting valves.
On the job
- Set the limit stop when you trim out the valve, then check the water at the showerhead with a thermometer. Write the setting down for the file.
- Look for the ASSE 1016 marking on the valve body or cartridge before the wall is closed. Replacing an unmarked valve after the tile is up is the expensive way.
- Gang showers, such as locker rooms and gyms, get one ASSE 1069 mixing valve for the group, field-adjusted to the maximum temperature.
The inspector and your city's adopted edition have the final word.