The rule
Pre-rinse spray valves in commercial food service have a maximum flow rate set by Table 420.3, and each one has to have an integral automatic shutoff.
The table sorts valves by spray force. Product Class 1, at 5.0 ounces-force or less, is limited to 1.00 gpm. Class 2, over 5.0 and up to 8.0 ounces-force, is limited to 1.20 gpm. Class 3, over 8.0 ounces-force, is limited to 1.28 gpm.
The automatic shutoff means the valve closes when it's released, instead of running until someone turns it off.
On the job
- Check the spray-force class on the valve's spec sheet or packaging, and match it to the limit in the table. A valve without a marked class is hard to approve.
- Confirm the valve has the integral shutoff before it goes on the dish-room hose reel.
- Section 401.3 adds that if state appliance law has a lower flow limit, the lower one applies.
The inspector and your city's adopted edition have the final word.