The rule
The occupant load and the occupancy classification come from the California Building Code (or Table 4-1, the occupant load factor table, as the section allows). Then Table 422.1 gives the minimum fixtures for that occupancy. If an occupancy isn't in the table, the Authority Having Jurisdiction considers it separately.
The minimum number of fixtures is calculated at 50 percent male and 50 percent female of the total occupant load, unless the submitted information shows a different split. When the ratios produce fractions, round up to the next whole number. For multiple occupancies, add the fractions first and round after. Substituting a water closet for each urinal is permitted as long as the total still meets Table 422.1.
There are exceptions. Residential installations are exempt from the male and female split. So are occupancies with a total occupant load of 10 or less, where one single-user toilet facility can serve both sexes. Business and mercantile occupancies with a load of 50 or less get the same allowance. And separate facilities aren't required where the fixtures are designed for both sexes and the water closets are in privacy compartments.
The table also covers the dwelling case: a one or two family dwelling needs one water closet, one lavatory, one bathtub or shower, and a kitchen sink plus an automatic clothes washer connection. For accessibility, use Chapter 11A or 11B of the California Building Code.
On the job
- Worked example: a business occupancy with 100 occupants is 50 male and 50 female. Reading the Business row, the men need one water closet, one urinal and one lavatory, the women need three water closets and one lavatory, and the building needs one drinking fountain (one per 150 persons, and a fraction rounds up) plus one service sink or laundry sink. It's an illustration only, so confirm against the current table and the plans examiner.
- The table applies to new buildings, additions, and changes of occupancy or type in an existing building that increase the occupant load. A tenant improvement that changes occupancy can trigger it.
- Mind the table's notes. For example, the number of water closets for women can't be less than the number of water closets and urinals for men, and each urinal added above the minimum lets you drop one water closet, down to two-thirds of the minimum.
The inspector and your city's adopted edition have the final word.