The rule
Chapter 5 governs the construction, location and installation of water heaters that heat potable water, along with their chimneys, vents and connectors. For storage heaters, minimum capacity isn't judged by tank size. It's judged by first-hour rating: how many gallons the heater can deliver in one hour starting with a full tank. The number is on the Energy Guide label.
To use Table 501.1(2), count bathrooms first (1 to 1.5, 2 to 2.5, or 3 to 3.5), then bedrooms, and read the gallons. At 1 to 1.5 baths, 1 bedroom is 38 gallons and 2 bedrooms is 49. At 2 to 2.5 baths, 3 bedrooms is 62 and 5 bedrooms is 74. At 3 to 3.5 baths, 4 bedrooms is also 74. The table tops out at 74 gallons, and solar water heaters are sized to the same first-hour ratings.
Table 501.1(1) lists the product standard each type of heater is built to, such as UL 174 for household electric storage heaters. Gas-fired storage heaters at 75,000 Btu/h or less fall under one standard, and larger gas units or instantaneous ones fall under another. A listed heater goes in following the manufacturer's installation instructions. An unlisted one has to be approved under Section 504.3.2. Either way, the final installation has to be approved by the Authority Having Jurisdiction.
On the job
- Read the Energy Guide label before you order, not the nominal tank size on the box. Two heaters with the same tank capacity can have different first-hour ratings.
- Count bathrooms and bedrooms for the house as it stands today, including any addition since the old heater went in. An addition can push you into the next row.
- Tankless units are rated by flow instead, and this table is written for storage heaters. Ask the inspector how your city wants a tankless sizing shown.
The inspector and your city's adopted edition have the final word.