CPC 608.7 · Water heaters

Vacuum relief valve on a tank above the fixtures

If a hot-water storage tank or indirect water heater sits higher than the fixture outlets in the hot water system, it needs a vacuum relief valve complying with ANSI Z21.22/CSA 4.4, installed on the tank or heater.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

A hot water tank mounted above the fixtures with a vacuum relief valve on top of the tank, next to a tank below the fixtures that does not trigger the rule.
Tank above the fixture outlets: vacuum relief valve (ANSI Z21.22/CSA 4.4) on the tank or heater. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

When the tank is higher than the outlets it serves, draining the piping can pull a vacuum on the tank. A vacuum relief valve lets air in so the tank doesn't siphon empty or collapse.

The trigger is elevation: a hot-water storage tank or an indirect water heater located at an elevation above the fixture outlets in the hot water system. The valve goes on the tank or the heater, and it has to comply with ANSI Z21.22/CSA 4.4.

It's a separate device from the T&P valve, which handles heat and pressure going up, not a vacuum going down.

On the job

  • Compare the tank's elevation with the highest hot water outlet on the system. Attic and upper-floor heater installs and high-mounted indirect tanks are where this comes up.
  • Install the valve according to the maker's instructions and confirm it's listed to ANSI Z21.22/CSA 4.4.
  • A tank below the outlets isn't covered by this section's trigger.

The inspector and your city's adopted edition have the final word.