CPC 609.11 · Water supply and distribution

Water hammer arresters at quick-acting valves

Where quick-acting valves are installed, the water supply needs water hammer arresters that comply with ASSE 1010 or PDI-WH 201, installed as close as possible to the quick-acting valves. The 2025 CPC marks this section as not adopted by HCD.

2025 California Plumbing Code, Chapter 6 (Water Supply and Distribution) · Applies to: Homes and commercial buildings

A washing machine supply with an arrester installed on the line right at the quick-acting valve, compared with one installed far from the valve.
Approved mechanical arrester (ASSE 1010 or PDI-WH 201), as close as possible to the quick-acting valve. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

A quick-acting valve, such as a clothes washer or dishwasher solenoid, stops the flow in an instant. That stop slams the moving water and sends a pressure spike through the piping. The code requires water hammer arrester(s) to absorb those pressures.

Arresters have to be approved mechanical devices that comply with ASSE 1010 or PDI-WH 201, and they're installed as close as possible to the quick-acting valves they protect.

Where a listed mechanical device is used, follow the manufacturer's specifications for location and installation method.

On the job

  • Put the arrester at the appliance valve, not at the other end of the branch. As close as possible is the rule.
  • Check the arrester's listing and follow the maker's sizing and placement instructions for where it can go in the line.
  • The air chamber is not what the code approves here: the device is an approved mechanical device. Don't count on a capped stub of pipe.

The inspector and your city's adopted edition have the final word.