Home › Code Library › CPC 703.2

CPC 703.2 · Sanitary drainage and sewers

How many fixture units a drain pipe can carry

Table 703.2 limits the fixture units on a drain by pipe size. A horizontal 2 inch line carries up to 8 DFU, 3 inch up to 35, and 4 inch up to 216. A vertical drain also has a maximum height for its size.

2025 California Plumbing Code, Chapter 7 (Sanitary Drainage) · Applies to: Homes and commercial buildings

Table of maximum drainage fixture units and vertical length for 1-1/2, 2, 3 and 4 inch drain pipe, with a worked bathroom example and footnote reminders.
Add up the DFU, then pick the smallest pipe whose Table 703.2 limit covers it. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

You size drainage pipe by adding up the DFU of everything connected to it (Section 703.1), then looking up the smallest pipe whose limit covers the total. Vertical pipe is also checked against its length, because each size has a maximum vertical length.

Per Table 703.2, a horizontal line carries 1 DFU on 1-1/4 inch, 1 on 1-1/2, 8 on 2, 35 on 3, and 216 on 4 inch. Vertical limits run higher: 2 for 1-1/2 inch, 16 for 2, 48 for 3 and 256 for 4. Vertical maximum lengths are 65 feet for 1-1/2 inch, 85 for 2, 212 for 3 and 300 for 4. Horizontal length isn't limited.

The footnotes matter. A 2 inch pipe can't take water closets or six-unit traps. A 3 inch pipe can't take more than six water closets or five six-unit traps. The 4 inch and larger horizontal values assume 1/4 inch per foot of slope; at 1/8 inch per foot, multiply them by 0.8.

The table excludes the trap arm. Appendix C has an alternate sizing method if the inspector accepts it (Section 703.3).

On the job

  • Tally first, then pick the pipe. A common bathroom group is a tub (2), a lavatory (1) and a water closet (3), which is 6 DFU, and the water closet alone needs a 3 inch drain.
  • On a flat run where you've been allowed 1/8 inch per foot, the capacity drops. A 4 inch line then carries only 0.8 of the table's horizontal number, so recheck before you call the run good.
  • Upsizing is usually cheap and rarely a problem. Undersizing is the correction notice, so when a run is close to the limit, step up a size.

The inspector and your city's adopted edition have the final word.

Give us a call

Call (760) 912-9831