The rule
This is the rule that lets you put two lavatories on opposite sides of a wall, or two fixtures next to each other, on a single vertical pipe. It saves a stack and a lot of framing.
The condition is the fitting. Each fixture has to waste on its own into an approved double-fixture fitting, and the two inlets have to be at the same level. Each fixture still needs its own trap, and the pair has to stay within the distance the code allows between a trap and its vent.
The fitting is what keeps one fixture's discharge from being pushed back up into the other, so you can't swap in an ordinary cross or two ordinary tees at different heights and call it the same thing.
On the job
- Set the double-fixture fitting at the right height before you close the wall. Both trap arms have to arrive at the same level, so mock up the two fixture heights first.
- Check the trap-to-vent distance for each fixture separately, not just for the pair. The measurement runs from each trap's weir to its vent.
- Leave the fitting, trap arms and vent connection exposed for the rough inspection. They're hard to correct once the wall is closed.
The inspector and your city's adopted edition have the final word.