The rule
The minimum size of a building sewer comes from the total number of fixture units it drains, using Table 717.1. No building sewer can be smaller than the building drain it serves.
For sewers 6 inches and smaller, the sizing is as specified in Table 703.2, with no minimum loading. For 8 inch, 10 inch and 12 inch sewers, Table 717.1 gives a maximum and a minimum fixture unit loading for each slope: 1/16, 1/8 and 1/4 inch per foot. For example, an 8 inch sewer at 1/4 inch per foot is listed at 3900 maximum and 275 minimum.
So the slope you run changes the pipe's allowed load. A flatter slope takes fewer fixture units, which is why the table is organized by slope.
Appendix C has an alternate method for sizing building sewers if the inspector accepts it.
On the job
- Tally the fixture units for the whole building first, then pick the size, then check that the slope you can actually get supports that load.
- Don't step down at the property line or the house wall. The building sewer starts at least as large as the building drain.
- Check the maximum and the minimum with large sewers. They apply together.
The inspector and your city's adopted edition have the final word.