The rule
Water that turns a corner in a drain should do it with a gentle sweep so solids keep moving. For a horizontal line entering a vertical stack, the list is 45 degree wyes, 60 degree wyes, combination wye and eighth bends, sanitary tees or sanitary tapped tees, or other approved fittings with an equivalent sweep.
Don't use a fitting with more than one inlet at the same level unless it's built so the discharge from one inlet can't readily enter another. A plain cross or a pair of straight tees on the same plane is the usual violation.
Double sanitary tees are the exception, allowed where the barrel is at least two pipe sizes larger than the largest inlet. The recognized sizes for counting are 2, 2-1/2, 3, 3-1/2, 4, 4-1/2, 5 and 6 inch, so 2 inch inlets need a barrel of at least 3 inch.
On the job
- Set sanitary tees with the sweep pointing down, the way the water flows. A tee turned the wrong way is the classic mistake.
- When two branches have to enter at the same height, a double sanitary tee works only with the larger barrel. If the barrel can't be upsized, offset the two branches so they enter at different levels.
- Test-fit the wye and the bend together before you glue, so the branch keeps its slope after it enters the stack.
The inspector and your city's adopted edition have the final word.