The rule
Table 814.3 sets the minimum condensate pipe diameter by the tons of refrigeration. Up to 20 tons, it's 3/4 inch. For 21 to 40 tons, 1 inch. For 41 to 90, 1-1/4 inch. For 91 to 125, 1-1/2 inch. For 126 to 250, 2 inch. The size applies to one unit or a combination of units, or as the manufacturer recommends.
The table assumes a slope of 1/8 inch per foot (1 percent) with the pipe running three-quarters full. For other slopes or conditions, the AHJ approves the sizing.
Material has to meet the pressure and temperature rating of the equipment and be approved for the liquid it carries. Air-conditioning waste pipes 1-1/4 inch and larger use the materials in Chapter 7. Smaller lines can be PVC, CPVC, PE, PP, copper or other rigid materials the AHJ approves.
Condensate drain lines have to be arranged, or have a cleanout, so a blockage can be cleared without cutting the line.
On the job
- Check the combined tons on a shared line. The table covers one unit or a combination.
- Small residential units are 3/4 inch territory. Larger commercial rooftop or air handler lines move up the table quickly.
- Don't skip the cleanout or a way to rod or flush the line. A condensate line that can only be cleared by cutting it gets flagged.
- Condensate from a condensing appliance, like a furnace, is sized from the manufacturer's instructions in 814.4, not this table.
The inspector and your city's adopted edition have the final word.