The rule
Vent size comes from two things: how long the vent is and how many fixture units it serves, read from Table 703.2. On top of the table, an individual vent has to be at least 1-1/4 inches and at least half the diameter of the drain it connects to. A 3 inch drain needs a vent of at least 1-1/2 inches; a 4 inch drain needs at least 2 inches.
The building as a whole has a second test. The vents together have to have a cross-sectional area at least as big as the largest required building sewer. Vents upstream of a pump, an ejector, a backwater valve or anything else that blocks air from reaching the outside don't count toward that total.
There's an exception for two or more buildings on the same lot under one ownership that share a building sewer. Their drainage can be vented with piping sized from Table 703.2, as long as the vents together still equal the area of the largest common building sewer.
On the job
- Vents run at full size up through the roof (Section 905.4). Reducing the pipe at the roof line doesn't pass.
- A fixture upstream of a backwater valve or ejector pit can't count toward the building-vent area. Show a separate vent path on the plans.
- Pick the vent size from the table before you buy fittings, so a long run doesn't end up a size short.
The inspector and your city's adopted edition have the final word.