CPC 904.2 · Vents

Vent length: one-third horizontal on a minimum-size vent

On a minimum-sized vent, no more than one-third of the table's permitted length can run horizontally. Upsize the vent one pipe size for its whole length and the length limit no longer applies.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Homes and commercial buildings

A 2 inch minimum-sized vent drawn as 120 feet total, with 40 feet horizontal and 80 feet vertical, and the option to upsize one pipe size for the whole length.
A minimum-sized vent can have only one-third of its permitted length horizontal; upsize the whole vent one size and the limit goes away. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

Table 703.2 gives each vent size a maximum length. If you're using the smallest vent the table allows for the load, no more than one-third of that permitted length can be horizontal. A 2 inch vent at the table's 120 foot limit can have no more than 40 feet of it horizontal and the other 80 feet vertical.

Count the horizontal pieces together, wherever they fall in the run. Offsets and attic runs all add up toward the one-third limit.

If you increase a minimum-sized vent by one pipe size for its entire length, the maximum length limit doesn't apply. That's often the quick fix when a vent runs long: go up a size and stop counting feet.

On the job

  • Measure the developed length of the vent, from the connection to the open air, including offsets. Count the horizontal pieces separately.
  • When a vent has to wander across an attic, the fix is to upsize the whole vent one size, not just the long part.
  • Write the vent size and developed length on the rough-in sketch so it's easy to show at inspection.

The inspector and your city's adopted edition have the final word.