The rule
A horizontal wet vent lets one drain serve as the vent for the other fixtures in a bathroom group. All of the fixtures have to be on the same floor level, and only the fixtures in the bathroom group can connect to the wet-vented branch.
The dry vent connecting to the wet vent has to be an individual vent for the bidet, shower, or bathtub. One or two vented lavatories can serve as the wet vent. Only one wet-vented fixture drain or trap arm can discharge upstream of the dry-vented fixture drain. The dry vent connects according to the rules in Sections 905.2 and 905.3.
The wet vent itself is sized by the fixture units discharging into it: 2 inches minimum for 4 drainage fixture units or fewer, and 3 inches minimum for 5 or more. The water closet connects downstream of every other fixture on the wet vent. Any additional fixtures discharge downstream of the wet vent system and are conventionally vented.
Trap arm lengths follow Table 1002.2. Each vent opening on the wet vent, except for water closets and similar fixtures, can't be below the weir of the trap.
On the job
- Lay out the order before you rough: lavatory or lavatories upstream, then the dry-vented shower or tub, then the toilet last. Putting the toilet anywhere but last on the wet vent is the mistake to avoid.
- Add up the fixture units discharging into the wet vent. Four or fewer is 2 inch pipe, five or more is 3 inch.
- Anything that isn't part of the bathroom group, like a laundry sink, is vented conventionally and discharges downstream of the wet vent.
The inspector and your city's adopted edition have the final word.