The rule
A circuit vent lets one vent serve a whole run of fixtures on a horizontal branch, which suits restroom groups. The branch can have a maximum of eight floor-outlet water closets, showers, bathtubs or floor drains. Each trap arm connects horizontally to the branch, within the trap arm limits of Table 1002.2.
The vent connects to the branch on the vertical between the two most upstream trap arms. It's at least 2 inches and sized from Table 703.2 for the number of circuit-vented fixtures. The circuit vent pipe can't receive any soil or waste discharge. The branch itself is treated as a drain and a vent from the most downstream trap arm to the most upstream one.
When the branch serves four or more water closets and connects to a stack that takes soil or waste from upper branches, a 2 inch relief vent is added between the stack and the most downstream trap arm, installed on the vertical. The branch is sloped uniformly, no steeper than 1 inch per foot, and sized for the total load.
On the job
- Lay out the branch first. Count the fixtures, find the two most upstream trap arms, and put the vent between them.
- Don't forget the relief vent on a four-water-closet restroom that ties into a stack. It's a separate vent at the downstream end.
- Back-outlet and wall-hung water closets can be circuit vented too, as long as there are no floor-outlet fixtures on the same branch.
The inspector and your city's adopted edition have the final word.