Home › Code Library › CPC 911.1

CPC 911.1 · Vents

Circuit vent: up to eight fixtures on one branch

One horizontal branch can circuit vent up to eight floor-outlet water closets, showers, bathtubs or floor drains. The vent connects between the two most upstream trap arms and is at least 2 inches. A 2 inch relief vent is required where the branch takes four or more water closets and ties into a stack.

2025 California Plumbing Code, Chapter 9 (Vents) · Applies to: Commercial buildings

Four water closets on one horizontal branch with a circuit vent between the two most upstream, a relief vent near the stack, and notes on the eight fixture limit.
Up to eight fixtures on one branch, the circuit vent between the two most upstream trap arms, and a 2 in relief vent when four or more water closets connect to a stack. Diagram: Hoffman & Sons Plumbing (hoffmanandsons.com), CC BY 4.0. Free to share with credit. PNG · SVG · All diagrams

The rule

A circuit vent lets one vent serve a whole run of fixtures on a horizontal branch, which suits restroom groups. The branch can have a maximum of eight floor-outlet water closets, showers, bathtubs or floor drains. Each trap arm connects horizontally to the branch, within the trap arm limits of Table 1002.2.

The vent connects to the branch on the vertical between the two most upstream trap arms. It's at least 2 inches and sized from Table 703.2 for the number of circuit-vented fixtures. The circuit vent pipe can't receive any soil or waste discharge. The branch itself is treated as a drain and a vent from the most downstream trap arm to the most upstream one.

When the branch serves four or more water closets and connects to a stack that takes soil or waste from upper branches, a 2 inch relief vent is added between the stack and the most downstream trap arm, installed on the vertical. The branch is sloped uniformly, no steeper than 1 inch per foot, and sized for the total load.

On the job

  • Lay out the branch first. Count the fixtures, find the two most upstream trap arms, and put the vent between them.
  • Don't forget the relief vent on a four-water-closet restroom that ties into a stack. It's a separate vent at the downstream end.
  • Back-outlet and wall-hung water closets can be circuit vented too, as long as there are no floor-outlet fixtures on the same branch.

The inspector and your city's adopted edition have the final word.