The rule
Before you install a backflow device or assembly, the Authority Having Jurisdiction has to approve it. It has to be tested to a recognized standard and meet Table 603.2, except for the special cases in 603.5.1 through 603.5.22.
After it's in, the person who controls the device keeps it in good working condition. It gets tested when it's installed, repaired or moved, and then at least once a year, or more often if the AHJ requires. If it fails or doesn't work, it's repaired or replaced.
You can't take a device out of service, move it, or swap another one in without the AHJ's approval.
Testing and maintenance are done by a certified backflow assembly tester or repairer certified under ASSE/IAPMO/ANSI Series 5000, or another certification the AHJ accepts.
On the job
- Hand the owner a clear note on the annual test. The test is a recurring obligation of whoever controls the assembly, not a one-time job.
- Tag or log the test date at the assembly. If an inspector or the water supplier asks, the paperwork should be sitting there.
- Don't pull an old assembly to 'get it out of the way' on a remodel without sign-off. Relocating or substituting needs the AHJ's approval and a new test.
- Your local water supplier runs its own cross-connection program and may ask for more than the plumbing code does. Call them before you buy the assembly.
The inspector and your city's adopted edition have the final word.