The rule
In a wet vent, one vertical pipe serves as both drain and vent for the fixtures that connect to it. It's limited to the trap arms of one and two fixture unit fixtures, such as lavatories, showers and tubs, and not more than four fixtures in all.
The wet-vented fixtures have to be on the same story. A fixture that has its own continuous vent discharging into the wet vent has to be on that story too. The wet vent's developed length can't exceed 6 feet.
Size it by sections. The pipe between two consecutive inlet levels is one wet-vented section. Each section is a pipe size larger than the minimum waste size of the upper fixture, or a size larger than the minimum for the total fixture units that section serves, whichever is bigger, and never smaller than 2 inches. The common vent is sized for the sum of the fixture units served, but not smaller than the minimum vent for any fixture it serves.
On the job
- Count the fixtures before you commit. A fifth fixture, or any fixture above 2 fixture units, kicks you out of this section.
- Measure the developed length of the wet vent, not the straight distance between inlets, and keep it to 6 feet or less.
- Check the dfu values in Table 702.1 for each fixture. Only one and two fixture unit fixtures qualify.
The inspector and your city's adopted edition have the final word.