Combustion air volume check

Gas appliances in a room need enough air to burn. By the standard method, the room needs 50 cubic feet of volume for every 1000 Btu/h of total appliance input. A 40,000 Btu/h water heater needs 2,000 cubic feet.

Run the numbers

Appliances in the room (input rating, Btu/h)
The input rating is on the nameplate.
The room (feet)
Rooms that open into this one through openings with no doors, sized to Section 506.3.

Worked example

A storage water heater rated 40,000 Btu/h in a 20 by 20 foot garage with an 8 foot ceiling.

  1. Water heater: 40,000 Btu/h
  2. Total input = 40,000 Btu/h
  3. Required volume = 40,000 ÷ 1000 × 50 cubic feet = 2,000 cubic feet
  4. Room volume = 20 × 20 × 8 feet = 3,200 cubic feet

Result: Enough air: 3,200 cubic feet available, 2,000 required. That's 1,200 cubic feet to spare.

The same garage with a 35,000 Btu/h water heater and a 100,000 Btu/h furnace together.

  1. Water heater: 35,000 Btu/h
  2. Furnace: 100,000 Btu/h
  3. Total input = 135,000 Btu/h
  4. Required volume = 135,000 ÷ 1000 × 50 cubic feet = 6,750 cubic feet
  5. Room volume = 20 × 20 × 8 feet = 3,200 cubic feet
  6. Short by 6,750 − 3,200 = 3,550 cubic feet

Result: Not enough air by the standard method: 3,200 cubic feet available, 6,750 required. You're 3,550 cubic feet short.

What the code says

  • The standard method calls for 50 cubic feet of room volume per 1000 Btu/h of input (Section 506.2.1).
  • The total required volume is the sum for all the appliances in the space (Section 506.2).
  • Where the air infiltration rate is known to be under 0.40 air changes per hour, the known infiltration method in Section 506.2.2 is used instead.
  • Rooms that connect to the appliance space through openings with no doors, sized and placed per Section 506.3, count as part of the volume.
  • For two spaces on the same story, each opening needs at least 1 square inch of free area per 1000 Btu/h, and not less than 100 square inches. One opening starts within 12 inches of the top and one within 12 inches of the bottom, and the smallest dimension is 3 inches (Section 506.3).
  • Direct vent appliances are exempt from this section (Section 506.1). If the volume isn't enough, outdoor air comes in under Sections 506.4 through 506.7.3.

Method covered: the standard method of Section 506.2.1 only, plus the same-story opening size from Section 506.3. The known air infiltration method, outdoor air openings and ducts aren't calculated here. Appliance inputs come from each nameplate.

Read the full sections in the library: CPC 506.2 and CPC 506.3.

Sources

The inspector and your city's adopted edition have the final word. This tool is a summary of the code, not the code itself.