Home › Free Tools › Drain size by fixture units calculator

Free plumbing tool

Drain size by fixture units

Add up the fixtures and this tool gives you the total drainage fixture units (DFU) and the smallest drain pipe the 2025 California Plumbing Code allows. A typical one-bath house with a kitchen and laundry comes to 13 DFU and needs a 3 inch drain.

Run the numbers

Homes are private use.
How many of each fixture
Leave at 0 if there is none.

Worked example

A one-bath house, private use: one water closet, one lavatory, one tub/shower, a kitchen sink, a dishwasher and a clothes washer, horizontal run at 1/4 inch per foot.

  1. Water closet, 1.6 GPF, gravity tank: 1 × 3 DFU = 3 DFU
  2. Lavatory: 1 × 1 DFU = 1 DFU
  3. Bathtub or tub/shower combination: 1 × 2 DFU = 2 DFU
  4. Kitchen sink, domestic (with or without disposer or dishwasher): 1 × 2 DFU = 2 DFU
  5. Dishwasher, domestic, own drain: 1 × 2 DFU = 2 DFU
  6. Clothes washer, domestic, standpipe: 1 × 3 DFU = 3 DFU
  7. Total load = 13 DFU
  8. Horizontal drain at 1/4 inch per foot: 3 inch holds 35 DFU, which covers 13 (the next size down, 2 inch, holds 8).
  9. Vertical drain: 3 inch holds 48 DFU and can run up to 212 feet tall.

Result: 13 DFU needs 3 inch drain, horizontal or vertical.

A small public restroom group, public use: four water closets, four lavatories and two urinals, horizontal run at 1/4 inch per foot.

  1. Water closet, 1.6 GPF, gravity tank: 4 × 4 DFU = 16 DFU
  2. Lavatory: 4 × 1 DFU = 4 DFU
  3. Urinal, integral trap, 1.0 GPF: 2 × 2 DFU = 4 DFU
  4. Total load = 24 DFU
  5. Horizontal drain at 1/4 inch per foot: 3 inch holds 35 DFU, which covers 24 (the next size down, 2 inch, holds 8).
  6. Vertical drain: 3 inch holds 48 DFU and can run up to 212 feet tall.

Result: 24 DFU needs 3 inch drain, horizontal or vertical.

What the code says

  • Table 702.1 gives every fixture a DFU value. The value depends on the fixture and on whether the use is private (homes), public or assembly.
  • Table 703.2 lists the most DFU each drain size can carry, in one column for horizontal runs and one for vertical. Vertical drains also have a maximum length for their size.
  • A 2 inch drain can't take water closets or six-unit traps. A 3 inch drain can't take more than six water closets or five six-unit traps.
  • A kitchen sink, a domestic dishwasher, a laundry sink and a 1.0 GPF urinal call for a 2 inch minimum drain (Table 702.1 note 2).
  • At 1/8 inch per foot, multiply the horizontal DFU limits by 0.8. That slope is only for 4 inch and larger building drain piping, and only with approval (Section 708.1).
  • A pump, sump ejector or similar device counts as 2 DFU for every gallon per minute of flow (Section 702.3).
  • Up to 8 public lavatories may share a 1-1/2 inch branch at 1/4 inch per foot (Table 703.2 note 7).

Rows covered: 13 common fixtures from Table 702.1 (water closets, lavatory, tub, shower, kitchen sink, dishwasher, clothes washer, laundry sink, floor drain, drinking fountain, mop basin and urinal) and every drainage piping row of Table 703.2, 1-1/4 inch through 12 inch. Other fixtures, the Table 702.1(1) trap loadings and the Appendix C method aren't in this tool. It sizes by the total load only, so it doesn't check branch by branch, trap arms or vents.

Read the full sections in the library: CPC 702.1 and CPC 703.2.

Sources

The inspector and your city's adopted edition have the final word. This tool is a summary of the code, not the code itself.