Home › Free Tools › Water pressure check
Free plumbing tool
Water pressure check
The California Plumbing Code wants at least 15 psi of residual pressure at the fixtures and a pressure regulator when static pressure is over 80 psi. Enter your readings to see where you land.
Run the numbers
Worked example
A house with 95 psi static pressure at the meter, 40 psi residual at the farthest fixture, and a regulator set at 60 psi.
- Static pressure 95 psi is over 80 psi, so Section 608.2 calls for a pressure regulator (with a strainer) that brings it down to 80 psi or less.
- Pipe sizing pressure for Table 610.4 = 80 percent of the reduced pressure = 0.8 × 60 = 48 psi.
- Residual pressure 40 psi is at least the 15 psi minimum (Section 608.1).
Result: A pressure regulator is required. Residual pressure is enough.
A house on a hill with 62 psi static pressure and only 12 psi residual at the highest fixture.
- Static pressure 62 psi is 80 psi or less, so Section 608.2 does not call for a regulator.
- Residual pressure 12 psi is under the 15 psi minimum (Section 608.1), short by 3 psi.
Result: No regulator is required by 608.2. Residual pressure is too low.
What the code says
- Where the supply can't deliver at least 15 psi residual pressure after friction and other losses, a tank and pump or other means that provides 15 psi has to be installed. Fixtures that need more than 15 psi set a higher minimum (Section 608.1).
- Where static pressure is over 80 psi, an approved pressure regulator with a strainer is installed and brings it down to 80 psi or less. A regulator of 1-1/2 inches or larger doesn't need a strainer (Section 608.2).
- Pipe sizing with Table 610.4 uses 80 percent of the reduced pressure (Section 608.2).
- An approved expansion tank goes in the cold water piping downstream of each regulator. A system designed by a licensed plumbing contractor or registered design professional may use approved relief valves set at 100 psi or less instead (Section 608.2).
Sections covered: 608.1 (minimum residual pressure) and 608.2 (excessive pressure and the 80 percent sizing pressure). The tool compares your readings with those numbers. It doesn't size pipe or select a regulator, a booster pump or an expansion tank.
Read the full sections in the library: CPC 608.1 and CPC 608.2.
Sources
- 2025 California Plumbing Code (Cal. Code Regs. Title 24, Part 5), IAPMO read-only edition: Section 608.1, Section 608.2 and Table 610.4. Effective January 1, 2026.
- California Building Standards Commission: Title 24 codes, errata and supplements.
The inspector and your city's adopted edition have the final word. This tool is a summary of the code, not the code itself.